english Icono del idioma   español Icono del idioma  

Por favor, use este identificador para citar o enlazar este ítem: https://hdl.handle.net/20.500.12008/49736 Cómo citar
Registro completo de metadatos
Campo DC Valor Lengua/Idioma
dc.contributor.advisorFavre, Federico-
dc.contributor.advisorUrquiola, Ana-
dc.contributor.authorLicandro Errazola, Federico Hugo-
dc.date.accessioned2025-04-23T12:57:14Z-
dc.date.available2025-04-23T12:57:14Z-
dc.date.issued2024-
dc.identifier.citationLicandro Errazola, F. Air quality evaluation in Uruguayan operating rooms : Evaluation of parameters, practices and measures associated with air quality in Uruguayan hospitals using air quality reports and computational fluid mechanics [en línea] Tesis de maestría. Montevideo : Udelar. FI, 2024.es
dc.identifier.issn1688-2792-
dc.identifier.urihttps://hdl.handle.net/20.500.12008/49736-
dc.description.abstractThis thesis evaluates air quality in Uruguayan operating rooms, focusing on both general air quality principles and a specific case study of a surgical room. The work is divided into three main parts. The first part presents a literature review on air quality, covering key parameters such as temperature, humidity, ventilation, differential pressure, and particulate concentration. It also discusses national and international air quality standards, ventilation systems (TMA and LAF), and associated maintenance practices. Additionally, air quality evaluations from 41 operating rooms in Uruguayan hospitals are analyzed using air quality reports. The results reveal a general lack of knowledge about ventilation and differential pressure management, specially for TMA rooms, despite the similar risks presented by the more controlled LAF-operated rooms. The second part focuses in the design and validation of a computational fluid dynamics code implemented in openFOAM for air quality evaluation in indoor environments. The code is validated using reference experiments. The third part focuses on a case study involving a specific OR with LAF ventilation. The CFD model is implemented to assess the impact of a partial separation wall between the air supply inlet and ceiling exhaust outlets. Three scenarios are simulated: with the separation wall installed, with a shorter wall, and without the wall. Results indicate that the partial wall improves air quality across the entire room, reducing contaminant concentration by 10.7% and increasing ventilation eciency from 41.7% to 51.5%. Near the patient area, contaminant levels decrease by 8.32% compared to the scenario without the wall.es
dc.format.extent111 p.es
dc.format.mimetypeapplication/pdfes
dc.language.isoenes
dc.publisherUdelar. FI.es
dc.rightsLas obras depositadas en el Repositorio se rigen por la Ordenanza de los Derechos de la Propiedad Intelectual de la Universidad de la República.(Res. Nº 91 de C.D.C. de 8/III/1994 – D.O. 7/IV/1994) y por la Ordenanza del Repositorio Abierto de la Universidad de la República (Res. Nº 16 de C.D.C. de 07/10/2014)es
dc.subjectSurgical site infectiones
dc.subjectOperating Roomes
dc.subjectParticulate Matteres
dc.subjectComputational Fluid Dynamicses
dc.subjectAir Qualityes
dc.titleAir quality evaluation in Uruguayan operating rooms : Evaluation of parameters, practices and measures associated with air quality in Uruguayan hospitals using air quality reports and computational fluid mechanics.es
dc.typeTesis de maestríaes
dc.contributor.filiacionLicandro Errazola Federico Hugo, Universidad de la República (Uruguay). Facultad de Ingeniería.-
thesis.degree.grantorUniversidad de la República (Uruguay). Facultad de Ingeniería.es
thesis.degree.nameMagíster en Ingeniería Mecánica.es
dc.rights.licenceLicencia Creative Commons Atribución (CC - By 4.0)es
Aparece en las colecciones: Tesis de posgrado - Instituto de Ingeniería Mecánica y Producción Industrial

Ficheros en este ítem:
Fichero Descripción Tamaño Formato   
LIC24.pdfTesis de maestría6,37 MBAdobe PDFVisualizar/Abrir


Este ítem está sujeto a una licencia Creative Commons Licencia Creative Commons Creative Commons