Título: Influence of ambient temperature on current transformers used in power distribution networks.
Autor: Slomovitz, Daniel
Santos, Alejandro
Trigo, Leonardo
Tipo: Ponencia
Palabras clave: Ratio error, Phase-shift, Accuracy class
Fecha de publicación: 2019
Resumen: Most of current transformers (CT) used at power frequency in high voltage networks have little dependence of temperature on errors. Indeed, international standards do not propose any specific accuracy test varying the temperature. However, we have detected that some commercial units of CTs, used in power distribution systems, exhibit large temperature dependence in the range -5 °C to 40 °C. It is proposed to add, to standard CT accuracy tests, an additional one at different temperatures.
Editorial: SEMETRO
EN: SEMETRO – XIII Congresso Internacional de Metrologia Elétrica, Florianópolis, SC, Brasil, 24-27 nov 2019, p. 1-4
Citación: Slomovitz, D., Santos, A. y Trigo, L. Influence of ambient temperature on current transformers used in power distribution networks [en línea] EN : SEMETRO – XIII Congresso Internacional de Metrologia Elétrica, Florianópolis, SC, Brasil, 24-27 nov. Florianópolis : SEMETRO, 2019. 4 p.
Licencia: Licencia Creative Commons Atribución - No Comercial - Sin Derivadas (CC - By-NC-ND 4.0)
Aparece en las colecciones: Publicaciones académicas y científicas - Instituto de Ingeniería Eléctrica

Ficheros en este ítem:
Fichero Descripción Tamaño Formato   
SST19.pdfVersión definitiva487,1 kBAdobe PDFVisualizar/Abrir


Este ítem está sujeto a una licencia Creative Commons Licencia Creative Commons Creative Commons