Title: Influence of ambient temperature on current transformers used in power distribution networks.
Authors: Slomovitz, Daniel
Santos, Alejandro
Trigo, Leonardo
Type: Ponencia
Keywords: Ratio error, Phase-shift, Accuracy class
Issue Date: 2019
Abstract: Most of current transformers (CT) used at power frequency in high voltage networks have little dependence of temperature on errors. Indeed, international standards do not propose any specific accuracy test varying the temperature. However, we have detected that some commercial units of CTs, used in power distribution systems, exhibit large temperature dependence in the range -5 °C to 40 °C. It is proposed to add, to standard CT accuracy tests, an additional one at different temperatures.
Publisher: SEMETRO
IN: SEMETRO – XIII Congresso Internacional de Metrologia Elétrica, Florianópolis, SC, Brasil, 24-27 nov 2019, p. 1-4
Citation: Slomovitz, D., Santos, A. y Trigo, L. Influence of ambient temperature on current transformers used in power distribution networks [en línea] EN : SEMETRO – XIII Congresso Internacional de Metrologia Elétrica, Florianópolis, SC, Brasil, 24-27 nov. Florianópolis : SEMETRO, 2019. 4 p.
License: Licencia Creative Commons Atribución - No Comercial - Sin Derivadas (CC - By-NC-ND 4.0)
Appears in Collections:Publicaciones académicas y científicas - Instituto de Ingeniería Eléctrica

Files in This Item:
File Description SizeFormat  
SST19.pdfVersión definitiva487,1 kBAdobe PDFView/Open


This item is licensed under a Creative Commons License Creative Commons