dc.contributor.authorCasaravilla, Gonzaloes
dc.contributor.authorSalvia, Adrianaes
dc.contributor.authorBriozzo, Césares
dc.contributor.authorWatanabe, Edson Hes
dc.date.accessioned2019-07-03T16:36:02Z-
dc.date.available2019-07-03T16:36:02Z-
dc.date.issued2002es
dc.date.submitted20190703es
dc.identifier.citationCasaravilla, G., Salvia, A., Briozzo, C., Watanabe, E. H. Selective active filter with remote harmonic distortion control [en línea] 10th International Conference on Harmonics and Quality of Power, 2002. doi 10.1109/ICHQP.2002.122148es
dc.identifier.urihttps://hdl.handle.net/20.500.12008/21210-
dc.descriptionPostprintes
dc.description.abstractThis paper presents the calculation methods for the different filtering blocks of a selective active filter in order to minimize the active filter inverter size, keeping the harmonic emissions at the limits stated by the applicable regulations. Since it may be necessary to comply with the regulations at a remote place with respect to the active filter location, the method has been extended to this case. In order to validate the simulations, measurements which were made at a real application - and arc furnace - were used. Finally, the simulated results obtained with a remote hybrid filter were compared with those obtained when an active filter is installed directly at the place where the harmonic emission regulations must be met. The comparison shows that remote compensation is an alternative to be seriously considered. The results are similar to those obtained with local compensation and the cost may be substantially lower.es
dc.languageenes
dc.publisherIEEEes
dc.rightsLas obras depositadas en el Repositorio se rigen por la Ordenanza de los Derechos de la Propiedad Intelectual de la Universidad De La República. (Res. Nº 91 de C.D.C. de 8/III/1994 – D.O. 7/IV/1994) y por la Ordenanza del Repositorio Abierto de la Universidad de la República (Res. Nº 16 de C.D.C. de 07/10/2014)es
dc.subjectHarmonices
dc.subjectPower qualityes
dc.subjectActive filterses
dc.titleSelective active filter with remote harmonic distortion controles
dc.typeArtículoes
dc.rights.licenceLicencia Creative Commons Atribución – No Comercial – Sin Derivadas (CC - By-NC-ND)es